Table 3
Data on sprinkler piping reliability
From:
A review of sprinkler system effectiveness studies
Description
Source
Unit
Minimum
Mean
Maximum
Pipe array
(Ronty and Keski-Rahkonen
2004
)
failures/year
2.4 × 10
-6
3.3 × 10
-6
4.3 × 10
-6
Gasket failure
(Budnick
2001
)
failures/hour
5.00 × 10
-7
4.00 × 10
-6
1.20 × 10
-5